< Marsh Bellofram Group of Companies < Bellofram Precision Controls < Electro Pneumatics < T-1500
Type 1500 I/P & E/P Transducer
Downloadable Files:
Type 1500
Catalog Pgs. (680 KB)
Type 1500 I/P & E/P Transducers
  • Electrical Connections: Conduit 1⁄2" NPT or BSPT, Terminal Block, Hirschmann® Connectors (DIN 43 650-A)
  • Supply and Output Ports on Front and Back of Unit
  • Low Air Consumption
  • External Zero and Span Adjustments
  • Field Accessible Orifice
  • Electrical Conduit Connection Meets CE Requirements
  • Intrinsically Safe Versions (FM, CSA, ATEX Approvals)
  • NEMA 4X Version (FM, CSA Approvals) Excludes Terminal Block
Product Detail:

The Marsh Bellofram Type 1500 electro-pneumatic transducer converts an electrical signal to a proportional pressure output. It provides low-cost precision electro-pneumatic control to actuators, valves, positioners, final control elements and high-flow controls. Occupying a small overall footprint, Type 1500's compact size and accessibility to ports and adjustments allow the unit to be installed in space-constrained locations or in a manifold for multi-device control. DIN rail and manifold assemblies are available in kits that provide three, five or ten mounting points. An integral pneumatic volume booster is included to provide high flow capacity.ign to provide high flow capacity. (See specifications for flow data

Applications
• Valve actuators
• Valve positioners
• HVAC systems
• Material handling systems
• Paper handling controls
• Automation systems
• Liquid and gas processing systems

Part Numbers:
Create a Part Number:
9
6
X
X
X
X
X
X
X
6
0
NEMA 4X (Includes Approvals) Electrical Certification
9
Indoor Use/General Purpose
7
1/4 NPT Pneumatic Port Connection
8
1/4 BSPT
9
1/4 BSPP
1
4-20 MA DC Electrical Input
2
0-5 VDC
3
1-9 VDC
4
1-10 VDC
5
0-10 VDC
6
1-5 VDC
0
3-15 PSIG Pneumatic Output
1
3-27 PSIG
2
6-30 PSIG
3
0-15 PSIG
4
0-30 PSIG
5
0-60 PSIG
6
0-120 PSIG
0
1/2 NPT Electrical Connection
1
Terminal Block (not NEMA 4X)
2
Hirschmann Connection
3
1/2" BSPT Conduit (1/4" BSPT/BSPP Only)
0
Nitrile Elastomers
1
Fluorocarbon
0
FM, CSA & ATEX Intrinsically Safe Agency Approvals
1
None - General Purpose
Options:
  • Intrinsically Safe (FM, CSA, ATEX)
  • NEMA 4X (FM, CSA) Excludes Terminal Block
   
Product Contact:
Specifications:
Standard Range
Zero
Based
Hysteresis
<0.75% of span
<1.0% of span
Repeatability
<0.5% of span
<0.5% of span
Linearity (Independent)
<0.75% of span <1.0% of span for fluorocarbon units
<1.0% of span
Flow @ Mid Range
6.5 SCFM (Minimum) @ 15.0 psig / 1.0 BAR output pressure, 120 psig / 8.3 BAR supply pressure
9.0 SCFM (Minimum) @ 15.0 psig / 1.0 Bar output pressure,150 psig / 10.3 BAR supply pressure
Maximum Air Consumption
3 SCFH @ 15 psi / 1.0 BAR output pressure
18 SCFH @ Maximum output pressure
Exhaust Capacity
>1.0 SCFM @ 5 psi / 0.4 BAR above set point
>1.0 SCFM @ 5 psi / 0.4 BAR above set point
Supply Pressure Range
5 psi above maximum output up to 120 psig / 8.3 BAR maximum
0-15 units: 25-150 psig / 1.7-10.3 BAR0-30 units: 40-150 psig / 2.8-10.3 BAR0-60 units: 70-150 psig / 4.8-10.3 BAR0-120 units: 125-150 psig / 8.6-10.3 BAR
Weight
1.3 lbs
1.63 lbs
Port Size
1/4 NPT, BSPT, BSPP
1/4 NPT,  BSPT, BSPP
Supply Pressure Sensitivity
<2.5% of span for a supply pressure change of 15 psig / 1.0 BAR
<1.7% of span change in output pressure over full supply pressure range (0-120 units)
Temperature Range
-20°F to +150°F
-20°F to +150°F
Input Signal
4-20 mA DC, 0-5 VDC, 1-5 VDC, 1-9 VDC, 0-10 VDC, 1-10 VDC
4-20 mA DC, 0-5 VDC, 1-5 VDC, 1-9 VDC, 0-10 VDC, 1-10 VDC
Output Range
3-15, 3-27, 6-30 psig 0.2-1.0, 0.2-1.9, 0.4-2.1 BAR
0-15, 0-30, 0-60, 0-120 psig0-1.0, 0-2.1, 0-4.1, 0-8.3 BAR
Electrical Connections: Both the I/P & E/P versions are two-wire devices, plus a safety ground. The E/P requires a DC voltage input signal; example: 1 to 9 VDC. The I/P models require an input current of 4 to 20 mA.